SUN-60/75/80K-SG01HP3-EU-EM6
Higher yields / Safe & Reliable / Smart / User-friendly
The SUN-60K to 80K-SG01HP3-EU-EM6 is a high-performance three-phase hybrid inverter built for industrial-grade and large commercial solar applications. With dual MPPT inputs and compatibility with 48V low-voltage battery systems, it delivers superior energy conversion and flexible energy storage options. The inverter supports advanced grid interaction, peak shaving, and time-of-use modes, while ensuring high safety standards and smart energy management. Its robust IP65-rated construction, remote monitoring capabilities, and scalable design make it ideal for demanding, high-load solar installations with backup and off-grid capabilities.




100% unbalanced output
AC couple to retrofit existing solar system
Max. 10 pcs parallel for on-grid and off-grid operation
Support multiple batteries parallel
Max. charging/discharging current of 160A
High voltage battery, higher efficiency AC couple to retrofit existing solar system
6 time periods for battery charging/discharging
Support storing energy from diesel generator
Technical Specifications
| Model | SUN-60K-SG01HP3-EU-EM4 | SUN-75K-SG01HP3-EU-EM6 | SUN-80K-SG01HP3-EU-EM6 |
|---|---|---|---|
| Battery Input Data | |||
| Battery Type | Lithium-ion | ||
| Battery Voltage Range (V) | 160-1000 | ||
| Max. Charging Current (A) | 80+80 | ||
| Max. Discharging Current (A) | 80+80 | ||
| Charging Strategy for Li-ion Battery | Self-adaption to BMS | ||
| Number of Battery Input | 2 | ||
| PV String Input Data | |||
| Max. DC Input Power (W) | 90000 | 112500 | 120000 |
| Max. DC Input Voltage (V) | 1000 | ||
| Start-up Voltage (V) | 180 | ||
| MPPT Voltage Range (V) | 150-850 | ||
| Rated DC Input Voltage (V) | 650 | ||
| Max. Operating PV Input Current (A) | 36+36+36+36 | 36+36+36+36+36+36 | |
| Max. Input Short-Circuit Current (A) | 54+54+54+54 | 54+54+54+54+54+54 | |
| No. of MPP Trackers/No. of Strings per MPP Tracker | 4/2+2+2+2 | 6/2+2+2+2+2+2 | |
| AC Input/Output Data | |||
| Rated AC Input/Output Active Power (W) | 60000 | 75000 | 80000 |
| Max. AC Input/Output Apparent Power (VA) | 66000 | 82500 | 88000 |
| Rated AC Input/Output Current (A) | 91/87 | 113.7/108.7 | 121.3/115.9 |
| Max. AC Input/Output Current (A) | 91/87 | 113.7/108.7 | 121.3/115.9 |
| Max. Continuous AC Passthrough (grid to load) (A) | 200 | ||
| Peak Power off-grid (W) | 1.2 times of rated power, 10s | ||
| Power Factor Adjustment Range | 0.8 leading to 0.8 lagging | ||
| Rated Input/Output Voltage/Range (V) | 220/380V, 230/400V 0.85Un-1.1Un | ||
| Rated Input/Output Grid Frequency/Range(Hz) | 50/45-55, 60/55-65 | ||
| Grid Connection Form | 3L+N+PE | ||
| Total Current Harmonic Distortion THDi | <3% (of nominal power) | ||
| DC Injection Current | <0.5% In | ||
| Efficiency | |||
| Max. Efficiency | 97.60% | ||
| Euro Efficiency | 97.0% | ||
| MPPT Efficiency | >99% | ||
| Equipment Protection | |||
| Integrated |
DC Polarity Reverse Connection Protection, AC Output Overcurrent Protection, Thermal Protection, AC Output Overvoltage Protection, AC Output Short Circuit Protection, DC Component Monitoring, Overvoltage Load Drop Protection, Ground Fault Current Monitoring, Arc Fault Circuit Interrupter (optional), Power Network Monitoring, Island Protection Monitoring, Earth Fault Detection, DC Input Switch, DC Terminal Insulation Impedance Monitoring, Residual Current (RCD) Detection, Surge protection level | ||
| Surge Protection Level | TYPE II(DC), TYPE II(AC) | ||
| Interface | |||
| LCD/LED Display | LCD+LED | ||
| Communication Interface | RS485/RS232/CAN | ||
| Monitor Mode | GPRS/WIFI/Bluetooth/4G/LAN (optional) | ||
| General Data | |||
| Operating Temperature Range (°C) | -40 to +60°C, >45°C Derating | ||
| Permissible Ambient Humidity | 0-100% | ||
| Permissible Altitude | 3000m | ||
| Noise (dB) | ≤65 | ||
| Ingress Protection(IP) Rating | IP65 | ||
| Inverter Topology | Non-Isolated | ||
| Over Voltage Category | OVC II(DC), OVC III(AC) | ||
| Cabinet Size (WxHxD mm) | 606×927×314 (Excluding Connectors and Brackets) | ||
| Weight (kg) | 97.5 | ||
| Type of Cooling | Intelligent Air Cooling | ||
| Warranty | 5 Years/10 Years the Warranty Period Depends the Final Installation Site of Inverter, More info Please Refer to Warranty Policy | ||
| Grid Regulation | IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, C99, VDE-AR-N 4105 | ||
| Safety / EMC Standard | IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 | ||